ISO 9001 : 2008

CERTIFIED

MSD-GB-21C1-A-R

Type : Motorized Smoke Damper
Leakage Rating : Class – I
Blade Type : 3V Single Skin; A : Parallel Operation
Construction : Galvanized Steel (GI)

 

MSD B-21 Series is a high performance UL 555S Classified smoke damper with Class- I leakage rating, installed vertically or horizontally (with blades running horizontally) and is rated for airflow and leakage in either direction.

UL-555S Test Ratings

Leakage Rating : Class – I

Max Velocity : 2000 fpm

Max Operating Pressure: 4 in. w.g (1000 pa)

Operating Temperature : 250 °F (121°C) for ½ hr

Additional Test Ratings

Operating Temperature :250°C (482 °F) for 1 hr* (HKFSD)
:250°C (482 °F) for 2 hr* (HKFSD)

Standard Construction

Frame

16 gauge (1.4 mm – 1.7 mm) thick galvanized steel.

Blades

Parallel operated 3 ‘V’ type blade made of 16 gauge (1.4 mm – 1.7 mm) thick galvanized steel.

Blade Seals

Silicon rubber blade seals.

Jamb Seals

Stainless steel.

Jack Shaft

12 mm diameter Galvanized steel shaft.

Actuator

Honeywell, Belimo, Seimens (24V AC, 120V AC, 230V AC).

Sleeve

Minimum 0.9 mm, single section is field or factory installed.
Multiple section is factory installed.
Sleeve thickness as per NFPA table 3-4.6.3.

Optional Fittings

Retaining Angles

1½” x 1½” x 16 gauge (40 x 40 x 1.5 mm).

Thermal Response Device (TRD)

165°F (74°C).

Limit Switches

For BMS open / close indication.

Indicator

Externally mounted open, close visible Indicator.

Push Button

For manual reset of damper.

Transitions (R)

Neck adapter for round duct connections.

Junction Box

Smoke Detector

Model : MSD-GB-21C1-A/R UL 555S Damper meets the required standards of SMACNA, NFPA, IBC, BOCA, ICBO, UL.

Actuator location standard: Left side from rear view
(Jack shaft view)

Note :
FC : Fail Close in the event of Fire
FO : Fail Open in the event of Fire

* The temperature ratings are for Honeywell 20 Nm actuators
with thermal enclosures.

WHILE ORDERING INDICATE THE DAMPER IS FC/FO (FAIL CLOSE / FAIL OPEN)

Optional Construction (UL Certification N/A)

Frame : Stainless Steel 16 gauge (304/316L)

Blade : Stainless Steel 16 gauge (304/316L)

Request for Quotation

  • MSFD-GB-31C3-A-R

    Galvanized construction, 3-hour, Class 3 leakage at 350° F, 3V single skin blade, 4 in. wg, 2000 fpm, operating temperature 250° C up to 2 hours
    Read more
  • MSFD-GB-31C2-A-R

    Galvanized construction, 3-hour, Class 2 leakage at 250° F, 3V single skin blade, 4 in. wg, 2000 fpm, operating temperature 250° C up to 2 hours
    Read more
  • MSFD-GB-31C1-A-R

    Galvanized construction, 3-hour, Class 1 leakage at 250° F, 3V single skin blade, 4 in. wg, 2000 fpm, operating temperature 250° C up to 2 hours
    Read more