ISO 9001 : 2008

CERTIFIED

MSFD-GB-21C2-A-R

Type : Motorized Fire Smoke Damper
Fire Rating : 21 Series-1½ hour.
Leakage Rating : Class – II
Blade Type : 3V Single Skin; A : Parallel Operation
Construction : Galvanized Steel (GI)

 

MSFD B-21 Series is a high performance UL 555 / 555S Classified combination of fire and smoke damper with 1½hr. fire rating, installed vertically or horizontally (with blades running horizontally) and is rated for airflow and leakage Class – II leakage in either direction.

UL-555S Test Ratings

Fire Rating : 1½ hrs.

Leakage Rating : Class – II

Max Velocity : 2000 fpm

Max Operating Pressure: 4 in. w.g (1000 pa)

Operating Temperature : 250°F (121°C) for ½ hr- Class-II

Additional Test Ratings

Operating Temperature :250°C (482 °F) for 1 hr* (HKFSD)
:250°C (482 °F) for 2 hr* (HKFSD)

Standard Construction

Frame

16 gauge (1.4 mm – 1.7 mm) thick galvanized steel.

Blades

Parallel operated 3 ‘V’ type blade made of 16 gauge (1.4 mm – 1.7 mm) thick galvanized steel.

Blade Seals

Silicon rubber blade seals.

Jamb Seals

Stainless steel.

Jack Shaft

12 mm diameter Galvanized steel shaft.

Thermal Response Device (TRD)

165°F.

Actuator

Honeywell, Belimo, Seimens (24V AC, 120V AC, 230V AC)

Sleeve

Minimum 0.9 mm, single section is field or factory installed.
Multiple section is factory installed.
Sleeve thickness as per NFPA table 3-4.6.3.

Limit Switches

For BMS open / close indication.

Optional Fittings

Retaining Angles

1½” x 1½” x 16 gauge (40 x 40 x 1.5 mm).

Indicator

Externally mounted open, close visible Indicator.

Push Button

For manual reset of damper.

Transitions (R)

Neck adapter for round duct connections.

Junction Box

Model : MSFD-GB-21C2 -A/R UL 555/555S Damper meets the required standards of SMACNA, NFPA, IBC, BOCA, ICBO, UL.

Actuator location standard: Left side from rear view
(Jack shaft view)

Note :
FC : Fail Close in the event of Fire
FO : Fail Open in the event of Fire

* The temperature ratings are for Honeywell 20 Nm actuators with thermal enclosures.

Optional Construction (UL Certification N/A)

Frame : Stainless Steel 16 gauge (304/316L)

Blade : Stainless Steel 16 gauge (304/316L)

Downloads

Request for Quotation

  • MSFD-GB-31C3-A-R

    Galvanized construction, 3-hour, Class 3 leakage at 350° F, 3V single skin blade, 4 in. wg, 2000 fpm, operating temperature 250° C up to 2 hours
    Read more
  • MSFD-GB-31C2-A-R

    Galvanized construction, 3-hour, Class 2 leakage at 250° F, 3V single skin blade, 4 in. wg, 2000 fpm, operating temperature 250° C up to 2 hours
    Read more
  • MSFD-GB-31C1-A-R

    Galvanized construction, 3-hour, Class 1 leakage at 250° F, 3V single skin blade, 4 in. wg, 2000 fpm, operating temperature 250° C up to 2 hours
    Read more