CERTIFIED
Type : Tunnel Ventilation Fire Damper
Fire Rating : 4 hours as per BS 476
Blade : Aerofoil Type
Construction : Galvanized Steel (GI)
BETEC CAD’s Ventilation Dampers are designed to isolate sections of a ventilation system with very high level of sealing. The dampers are mounted in side of the tunnel or at tunnel ends to control the pressurized air, air intake and smoke exhaust in long tunnels without intermediate supplies.
In emergency situations , for fire and smoke control, the dampers pressurize the tunnel for safe egress of train, automobile, passengers to escape and creates a negative pressure in the area of the fire to remove smoke and gases.
BETEC CAD’s Tunnel Ventilation Dampers are heavy duty and robust dampers requiring less maintenance and are suitable for high humidity, high pressure, dust laden environments making them ideal for installation and operation in Tunnels, Oil & Gas, Marine and Nuclear applications.
Fire Rating : 4 hrs vertical / 3 hrs horizontal as per BS 476
Air Velocity : 4000 fpm (20 m/sec)
Pressure : 8″ water gauge (2KPa).
Max . Holding Pressure : 20” W.g (5Kpa)
Fatigue cycles : 3.5 million simulated transient pressure reversals (under process)
14 gauge (2 mm) thick galvanized steel sheet with 2″ (50mm) external flanges.
Aerofoil blades of 14 gauge (2 mm) thick roll formed galvanized steel.
300°C high temp, resistant Silicon rubber blade seals.
Stainless steel.
High temperature resistant concealed ball bearings.
¾” (19 mm) diameter.
Pneumatic.
For Open / Close Indication.
Pressure drop for Dampers
WhatsApp us